4.255 min · Expert

POTT, Weak-Infeed Echo & Three-Terminal Lines

Pilot schemes that work when one end cannot see the fault.

You will be able to
  • ▸Compare POTT and DCB behaviour with a weak IBR terminal
  • ▸Implement weak-infeed echo and trip logic
  • ▸Recognise infeed/outfeed on three-terminal lines and current-reversal guard timing
  • ▸Supervise echo and weak-infeed trip on multi-terminal lines, and plan the channel-loss fallback
  • ▸Budget channel latency for Mirrored Bits and GOOSE
Standards
IEEE C37.113IEC 61850-8-1IEEE C37.94
Intuition

Why line protection needs a phone call

A distance relay at one end of a line cannot tell a fault at 95 % of the line from one just past the remote bus; CT/VT and line-impedance errors blur the boundary. So Zone 1 is set short (typically ≈ 80 %) and trips instantly, and Zone 2 over-reaches (typically ≈ 120 %) but waits, commonly 15–30 cycles (20 in the lab). That leaves the last 20 % of the line cleared slowly from one end.

Pilot schemes fix this by letting the two relays talk. Each tells the other what it sees, “fault is in front of me” or “fault is behind me”, and both can trip at high speed for any internal fault. The two classic philosophies are:

  • POTT (Permissive Overreaching Transfer Trip): trip if my overreaching forward element sees it and the remote says it sees it too. Secure by default, because a missing signal means no pilot trip.
  • DCB (Directional Comparison Blocking): trip if my forward element sees it and no block arrives from the remote within a coordination time. Dependable by default, because a missing signal means trip.

Both assume each terminal can see the fault. For phase faults an IBR plant terminal often cannot: the inverters' positive- and negative-sequence current is limited to roughly their rating, so 21 and 32Q/67Q forward elements may never pick up. That is the weak-infeed problem, and solving it is the topic of this module. Ground faults are different: as Module 4.1 shows, the grounded-wye winding of the MPT makes the plant end a strong, passive zero-sequence source, so 67G/32G elements there usually see ground faults well.

Comparison

POTT vs DCB at a glance

POTTPUTTDCBDCUB
Signal sent whenLocal forward (overreach) element picks upLocal Zone 1 (underreach) picks upLocal reverse element picks upLocal forward element picks up (FSK shifts from guard to trip)
Trip whenLocal forward AND permissive receivedLocal overreach AND permissive receivedLocal forward AND no block received after CC timerLocal forward AND (trip shift received, OR guard lost briefly without trip shift)
Channel failureLoses high-speed trip (secure)Loses high-speed trip (secure)May over-trip on external faults (less secure)Short unblock window on loss of guard, then blocks and alarms
Weak terminalNeeds echo + weak-infeed trip logicWeak end has no Zone 1 to key, so the strong end loses its pilot trip beyond its own Zone 1; the weak end cannot use a received permissive either, because its overreaching element does not pick upStrong end trips fast; weak end may never tripSame as POTT: needs echo + WEI
Speed penaltyNone beyond channel timeNone beyond channel timeEvery internal trip waits the CC timeNone beyond channel time
Typical channelFibre / digital (Mirrored Bits, GOOSE, C37.94), or FSK power-line carrierSame as POTT; rarely used on IBR tiesOn/off power-line carrier (a few ms)FSK power-line carrier, whose signal must cross the faulted line
DUTT (direct underreaching transfer trip) is not listed: the receiver trips on receipt with no local supervision, so it is used as an add-on to the schemes above and needs a secure channel.
Simulator

Watch the schemes race

The lab opens on the classic failure: a 2-terminal POTT line, an internal fault at 85 % (beyond the strong end's Zone 1) and a weak IBR at B. Press play, then step the scheme through + Echo and + Echo + WEI. Then try the security cases (“Behind A”, “Behind B”, “Reversal”) and the three-terminal tap with outfeed.

Interactive lab
Teleprotection state machine: DCB, POTT, echo and weak-infeed trip
Pick a scheme and a fault, then watch element pickups, channel bits and breaker operations unfold in time. Permissive (indigo), echo (cyan), block (red) and DTT (orange) bits travel the channel with the latency you set. US convention: red breaker = closed, green outline = open. Element timing is representative: forward 12 ms, reverse 8 ms, breaker 50 ms, Zone 2 333 ms.
Line
Pilot scheme
Terminal B source
Fault
85%
Zone 1 at A reaches 80 %. Faults beyond it need the pilot scheme.
4 ms
20 ms
Blocks keying/tripping after a reverse element drops out.
Failure to trip at B
The weak IBR terminal has no trip decision inside 450 ms. Without echo / weak-infeed logic it can only act after the remote breakers open, through time-delayed zones, or not at all, leaving the plant feeding the fault.
teleprotection channel · 4 ms one-wayABIBRfaultRelay AutilityZ1Z2 fwdZ3 rev27 UVPT txPT rxECHOguardTRIP52 openRelay BIBR · weakZ1Z2 fwdZ3 rev27 UVPT txPT rxECHOguardTRIP52 opent = 0.0 ms
0 ms
Relay A
trip @ 344.0 ms
Zone 2 time delay
Relay B
no trip
never reached a trip decision
Sequence-of-events timeline (click or drag to scrub)
050100150200250300350400450msAZ2 fwdZ3 revPT txECHOPT rxTRIP52 open▲ Zone 2 time delayBZ2 fwdZ3 revPT txECHOPT rxTRIP52 open
PT permissiveECHOBLOCKDTT
Logic

Echo and weak-infeed trip, gate by gate

Echo turns the weak terminal into a mirror. When it receives a permissive and sees nothing itself (no forward, no reverse), it sends the permissive straight back, so the strong end can trip. The preconditions are what keep it secure:

  • No reverse element and no guard timer. If the fault is behind the weak terminal, echoing would trip the healthy line.
  • Echo pickup delay (a few ms) rides through channel noise and brief permissive blips.
  • Echo duration and block timer. The echo is a fixed pulse (3–4 cycles), then echo is blocked for a while so two echoing terminals cannot latch the channel in a loop.
  • Open-breaker echo. If the local breaker is open, echo any permissive, so the remote can trip at high speed for an end-of-line fault.
  • Weak-infeed trip = echo conditions AND local undervoltage (27) or zero-sequence overvoltage (59N) AND breaker closed. Voltage supervision proves a real nearby fault before the weak end trips itself.
  • Multi-terminal lines. On a three-terminal line, echo and weak-infeed trip must require the permissive from all remotes, or be disabled. Otherwise one remote's permissive for an external fault, plus the voltage dip, trips the weak tap. Pair the rule with open-breaker keying at each remote, or an open remote strands the tap. The Topology section and the lab show this case.
Interactive lab
Echo and weak-infeed trip logic
Toggle the relay inputs and follow the energised (indigo) paths. This is a simplified version of the logic in most numerical line relays; check your relay's manual for exact timer names and defaults.
PT rxZ2 fwdNOTZ3 revNOTguardNOTecho blockNOT52 open27 / 59NAND 1(52 closed)AND 2ORpickup 2 msdur. 3–4 cycECHO → key PTlocal forward (not guarded) also keys PTAND 3WEI TRIP(52 closed)
PT transmit: KEYED
Echo: echoing
Weak-infeed trip: TRIP local breaker
Security

Current reversal on parallel lines

On double-circuit or parallel paths, sequential clearing of an external fault on the other line can reverse the current in the healthy line within a cycle or two. Before the reversal, terminal A sees forward and keys a permissive; B sees reverse. After the near-B breaker on the faulted line opens, A sees reverse and B sees forward. But A's permissive is still in flight, delayed by A's element dropout plus the channel time. If B's forward element picks up while that stale permissive is still arriving, POTT trips the healthy line.

The current-reversal guard blocks keying and tripping for a set time. In common relay implementations the extension starts when the local reverse element drops out, and it must outlast the remote's stale permissive: the remote forward element's dropout plus the channel's reset time, plus margin. Nothing is subtracted for the local forward pickup, because the local forward element can pick up almost as soon as the reverse element resets. Vendors name this timer differently: SEL calls it the Zone 3 reverse-block delay (Z3RBD), and other relays call it current-reversal guard or transient blocking. Check the manual for when your relay starts timing.

Tguard  ≥  tdropout, remote fwd+tch+marginT_{guard} \;\ge\; t_{dropout,\,remote\ fwd} + t_{ch} + \text{margin}
Topology

Three-terminal lines: infeed and outfeed

Tapping a collector substation into an existing line creates a three-terminal line, and two new effects appear:

  • Infeed: current from the tap raises the voltage seen by the outer terminals, so their distance elements under-reach. Zone 1 may not cover the faulted section at all, as at terminal C in the lab.
  • Outfeed: if an external path connects a terminal's bus back into the network (for example a parallel line from C's bus to A's), an internal fault near A can draw current out of the line at C. C's relay declares reverse and withholds its permissive. A three-terminal POTT needs permissives from both remotes, so the pilot trip is lost everywhere. Outfeed needs that external path, so it is a feature of utility terminals; a radial IBR tap has no path back to the network and rarely sees outfeed for phase faults. The lab therefore places it at C. Treat the lab's outfeed toggle as a logic demonstration of a terminal declaring reverse for an internal fault: with strong sources at A and C and a weak, current-limited tap, C would normally see infeed for a fault on the A–tap leg. Real outfeed needs a source strong enough to push current through the line and out at C, which an outfeed study has to show.
  • Weak-infeed echo at the tap: for a fault behind A, C keys its permissive and the weak tap sees only the voltage dip. If the tap echoes on any remote's permissive, its weak-infeed trip fires for an external fault. Require the permissive from all remotes before echoing (the lab's default), or disable echo and WEI on multi-terminal lines. The rule has a dependability cost: any remote that cannot key (an outfeeding terminal, or an open breaker) strands the tap. Pair it with open-breaker keying at each remote. The timeline lab does not model open-breaker keying (it appears only in the logic lab), so with outfeed on and the rule on, B never trips; with the rule off, B trips by WEI at 21 ms on the 8 ms channel.

Mitigations for outfeed include Zone-1-initiated direct transfer trip (DUTT) to all terminals, hybrid echo logic supervised by pilot-blocking zones, sequential-trip logic that re-evaluates once the first breaker opens, and line current differential where the channel allows. DUTT only helps when the fault is inside some terminal's Zone 1: in the lab it clears all three terminals at high speed for a fault at 60 % from A, but at 85 % no Zone 1 picks up: A waits for Zone 2 (344 ms), and B and C are left to time-delayed or sequential clearing (in the lab neither trips within the 450 ms window). Because a DUTT receiver trips with no local supervision, its channel needs security: a dual channel, a continuously monitored guard tone, or security counts.

Channels

Teleprotection channels and latency budgets

ChannelTypical one-way timeNotes
SEL Mirrored Bits over direct fibre≈ 3–6 ms back-to-back (representative)Point-to-point, deterministic, continuous channel monitoring; 8 logic bits each way. Mirrored Bits is SEL's protocol; other vendors have equivalent relay-to-relay protocols
IEEE C37.94 multiplexed fibre≈ 5–10 ms incl. muxStandard optical interface into SONET/SDH or packet multiplexers; watch asymmetric paths
IEC 61850 GOOSE (LAN) / R-GOOSE (WAN)< 4 ms in a station LAN; WAN depends on networkRequires engineered VLANs/priority and dataset supervision; IEC 61850-90-5 for routable GOOSE
Audio tone over microwave / leased≈ 8–15 msLegacy; susceptible to noise; often used for DTT with security counts
Power-line carrier, on/off (DCB)≈ 2–5 ms (representative)The classic DCB channel. Speed is why DCB pairs with carrier. The block is only needed for external faults, so it travels over the healthy protected line
Power-line carrier, FSK (POTT / DCUB)≈ 5–15 ms (representative; depends on bandwidth and security settings)Frequency-shift carrier with continuous guard tone; used for permissive and unblocking schemes. The trip shift must cross the faulted line itself
Values are representative. Always use measured channel times from commissioning tests in your settings calculations.
Key takeaways
  • POTT is secure by default, DCB is dependable by default. On IBR tie-lines POTT with echo + weak-infeed trip is the usual choice.
  • Echo lets the strong end trip at high speed; weak-infeed trip (echo + 27/59N) lets the weak end trip itself.
  • Echo must be blocked by reverse elements, guard timers and an echo-block timer, or it becomes a false-trip generator.
  • DCB coordination time and the POTT current-reversal guard both come from channel latency and element timing. Budget them explicitly.
  • Three-terminal taps add infeed (under-reach), outfeed (lost permissives) and echo/WEI security risks. Require permissives from all remotes (with open-breaker keying), plan DUTT/hybrid logic, or avoid the tap.
  • Define the channel-loss fallback (alarm, stepped distance, breaker-failure DTT) and check its clearing times.
Assessment

Knowledge check

0/8 answered
  1. Q1
    On a 2-terminal POTT line, the IBR terminal's forward elements never pick up for an internal fault. Without echo logic, what happens?
  2. Q2
    Which condition must block the weak terminal from echoing a received permissive?
  3. Q3
    What does the weak-infeed TRIP add on top of echo?
  4. Q4
    A DCB scheme uses a tone channel with 12 ms latency. Reverse elements pick up in 8 ms and forward elements in 12 ms. What is the minimum carrier-coordination time (CC), before margin?
  5. Q5
    During a parallel-line current reversal, why can a POTT terminal trip falsely?
  6. Q6
    On a three-terminal line, current outfeed at one utility terminal causes which problem for POTT?
  7. Q7
    Why is DCB less attractive than POTT + echo for an IBR tie-line?
  8. Q8
    On a three-terminal line with a weak IBR tap, a fault occurs behind utility terminal A. C sees it as forward and keys; A sees reverse. What stops the tap from false-tripping by weak-infeed logic?
Mastery challenge

Eliminate sequential tripping on an IBR tie-line

A 2-terminal 230 kV tie-line connects a utility substation (A) to a 300 MVA BESS (B). The existing scheme is plain POTT on an FSK power-line carrier channel (8 ms one way, representative). Use the lab to design a replacement and document its timing.