ProtectionAcademy
Quick reference

The protection engineer's cheat sheet

Device numbers, standards and terms used throughout the pathway. Keep this tab open while you work through the labs.

IEEE C37.2

Device function numbers

21
Distance relay
Gen-tie phase/ground distance (21P/21G); generator system backup
24
Volts-per-hertz
MPT and generator overexcitation
25
Synchronism check
Closing a breaker across two live systems
26
Apparatus thermal device
Transformer top-oil / winding temperature (26Q, 49T)
27
Undervoltage
Ride-through-coordinated plant undervoltage; BF supervision cases
32
Directional power
Generator reverse power (anti-motoring)
40
Loss of field
Synchronous generator excitation failure
46
Negative-sequence current
Generator rotor heating from unbalance (I₂²t)
49
Machine or transformer thermal
Thermal-model overload of the MPT, generator or cables
50
Instantaneous overcurrent
Pad-mount arc-flash stages, feeder high-set, BF current detector
51
AC inverse-time overcurrent
Feeder, pad-mount, transformer backup
51V
Voltage-restrained (51V) or voltage-controlled (51C) overcurrent
Generator system backup, as an alternative to 21
52
AC circuit breaker
52a / 52b auxiliary contacts follow breaker position
59
Overvoltage
Plant overvoltage; 59N / 59G (3V₀ neutral displacement) on ungrounded systems and on feeders that can lose their ground source
60
Voltage or current balance
Loss of potential (60/LOP): blocks 21, 40, 51V and directional elements when a VT fuse blows
62
Time-delay relay
62BF breaker-failure timer
63
Pressure switch
Transformer sudden pressure (63SPR)
64
Ground detector
Generator stator ground (64G), field ground (64F)
67
AC directional overcurrent
67G/67Q directional ground on feeders and the gen-tie
71
Liquid or gas level
Transformer oil level (71Q)
78
Out-of-step
Generator pole slip; out-of-step blocking or tripping on lines
79
Reclosing relay
Deliberately omitted on 34.5 kV collector feeders
81
Frequency relay
81U/81O, coordinated with PRC-029-1 ride-through (IBRs) or PRC-024-4 (synchronous units)
85
Communications / pilot
POTT/DCB channel logic, DTT
86
Lockout relay
Hand-reset trip-and-block (86B, 86T, 86BF)
87
Differential
87B bus, 87T transformer, 87G generator, 87L line, 87N restricted earth fault
89
Line switch
Disconnect or ground switch; 89a/89b contacts feed zone switching
94
Tripping or trip-free relay
Auxiliary trip relay (self-resetting, unlike the hand-reset 86)
Naming

Common suffixes

P / G / N
Phase, ground (residual or ground CT), neutral
Q
Negative-sequence quantity (e.g. 50Q, 32Q, 67Q)
V
Voltage-polarised (e.g. 32V zero-sequence impedance directional). Vendor nomenclature (SEL); other vendors name these elements differently
B / T / L / M
Bus, transformer, line, motor/machine zone
BF
Breaker failure: a suffix, not a base device (50BF, 62BF)
U
Unrestrained (87U high-set)
F / R
Forward / reverse looking (50QF, 50QR). Vendor nomenclature (SEL), not IEEE C37.2
Library

Governing standards

IEEE 2800-2022
Interconnection and interoperability of IBRs with transmission systems: ride-through, fault current, measurement
NERC PRC-024-4
Frequency and voltage protection settings for synchronous generators, Type 1/2 wind and synchronous condensers. Effective 1 Oct 2026; IBRs moved to PRC-029-1
NERC PRC-028-1
Disturbance monitoring and reporting requirements for IBRs. Effective 1 Apr 2025, with compliance phased in by facility
NERC PRC-029-1
Frequency and voltage ride-through requirements for IBRs. Effective 1 Oct 2026 (FERC Order No. 909); PRC-029-2 (revised exemption criteria) pending at FERC
NERC PRC-030-1
Unexpected IBR event mitigation: analysis and corrective action plans. Enforceable 1 Oct 2026
NERC PRC-002-5
Disturbance monitoring and reporting requirements (BES buses and elements)
NERC PRC-004
Protection system misoperation identification and correction
NERC PRC-005
Protection system, automatic reclosing and sudden-pressure relaying maintenance
NERC PRC-019
Coordination of generating-unit voltage regulating controls (UEL/OEL limiters) with protection
NERC PRC-025
Generator relay loadability (applies to synchronous and IBR plant relays)
NERC PRC-027
Coordination of protection systems for performance during faults (with the TO)
NERC MOD-026 / MOD-027
Verification of generator models (excitation/voltage control, and frequency/active power)
NERC TPL-001 (P5)
Planning events including protection-system single points of failure
NERC FAC-001 / FAC-002
Facility interconnection requirements and interconnection studies
IEEE C37.2
Electrical power system device function numbers, acronyms and contact designations
IEEE C37.91
Guide for protecting power transformers
IEEE C37.102
Guide for AC generator protection
IEEE C37.106
Abnormal-frequency protection for power generating plants
IEEE C37.110
Guide for the application of current transformers used for protective relaying
IEEE C37.113
Guide for protective relay applications to transmission lines
IEEE C37.118
Synchrophasor measurements
IEEE C37.119
Guide for breaker failure protection of power circuit breakers
IEEE C37.234
Guide for protective relay applications to power system buses
IEEE C37.242
Synchronization, calibration, testing and installation of PMUs (time sync)
IEEE C37.246
Protection of transmission-to-generation interconnections
IEEE C37.95
Protective relaying of utility-consumer interconnections
IEEE C37.101
Generator ground protection
IEEE C57.13
Instrument transformers (CT accuracy classes); C57.13.3 covers CT/VT secondary grounding
IEEE C57.109
Liquid-immersed transformer through-fault current duration (damage curves)
IEEE C37.111
COMTRADE: common format for transient data exchange
IEEE C37.112
Inverse-time characteristic equations for overcurrent relays
IEEE C62.92.1
Neutral grounding in electrical utility systems: introduction and effective grounding
IEEE C62.92.6
Neutral grounding of systems supplied by current-regulated sources (inverter-fed systems)
IEEE C62.22
Application of metal-oxide surge arresters (TOV capability)
IEEE C57.32
Neutral grounding devices (grounding transformer ratings)
IEEE 80
Safety in AC substation grounding (step/touch, GPR)
IEEE 1584-2018
Arc-flash hazard calculations (AC only; DC arc flash is outside its scope)
NFPA 70E
Electrical safety in the workplace: incident-energy analysis or PPE-category method (not both)
NEC Article 691
Large-scale photovoltaic electric supply stations
IEEE 1547-2018
DER interconnection (distribution); useful context for IBR TOV and ride-through concepts
IEEE 2800.2
Test and verification procedures for IEEE 2800 conformance (verify current status)
IEC 61850
Substation communication: GOOSE, Sampled Values, MMS

NERC status checked October 2026. Standards are revised regularly and NERC requirements phase in on their own dates (BES and non-BES IBRs differ), so always confirm the current edition and the implementation plan dates that apply to your facility.

Terms

Glossary

IBR
Inverter-based resource: solar PV, BESS and Type 3/4 wind, interfacing through power electronics.
POI / RPA
Point of interconnection; reference point of applicability where IEEE 2800 performance is measured.
Collector system
The MV (typically 34.5 kV) cable network gathering power from pad-mount transformers to the substation bus.
MPT / GSU
Main power transformer / generator step-up transformer between the collector and the transmission voltage.
COG
Coefficient of grounding: the highest sound-phase L–G voltage during a ground fault divided by the L–L voltage.
TOV
Temporary overvoltage: power-frequency overvoltage lasting cycles to seconds (e.g. during ground faults or islanding).
Weak infeed
A line terminal whose fault contribution is too small or unusual to operate conventional elements.
POTT / DCB
Permissive overreaching transfer trip / directional comparison blocking pilot schemes.
DTT
Direct transfer trip: an unsupervised trip command sent to a remote breaker.
CFIDS / VFIDS
Current- and voltage-based fault identification (faulted-phase selection) logic. CFIDS is SEL nomenclature; "VFIDS" is this course's label for the voltage-based equivalent.
Grid-forming (GFM)
An inverter controlled as a voltage source behind impedance (within its current limit), unlike the more common grid-following (current-source) IBR.
Grid-following (GFL)
An inverter that locks to the grid with a PLL and injects commanded current; most PV and BESS today.
Ferroresonance
Sustained overvoltage when VT magnetizing inductance resonates with system capacitance to ground; damped on broken-delta VTs with a loading resistor.
IT system
An LV system whose star point is not grounded; many utility-scale inverters require it and use an insulation monitor to detect the first ground fault.
PLL
Phase-locked loop: the inverter's estimate of grid voltage angle and frequency.
Momentary cessation
The inverter blocks current output during very low voltage without disconnecting.
CTI
Coordination time interval: the margin between upstream and downstream device operating times.
Remanence
Flux left in a CT core after a fault or DC test, which reduces headroom before saturation.