ProtectionAcademy
4.160 min · Expert

HV Tie-Line Ground Protection Near IBRs

Why CFIDS and 32Q fail, and how VFIDS, 32V and 67G restore coverage.

You will be able to
  • ▸Explain why 87L, 21G and 32Q misbehave with an IBR-only terminal
  • ▸Exploit the passive zero-sequence network behind the MPT
  • ▸Set 50GF, 32V thresholds and VFIDS for directional coverage of resistive faults up to 40 Ω
  • ▸Guard against induced zero-sequence loop current from mutual coupling making both ends declare forward
Standards
IEEE C37.113IEEE C37.246IEEE PES-TR81 (verify)
Intuition

One strong end, one weak end

A conventional transmission line is a tug-of-war between two big synchronous sources. Fault current pours in from both ends, and it lags the voltage by roughly the line angle at both ends. Line relays were designed around that symmetry. They compare currents between ends (87L), measure impedance (21), and judge direction from sequence quantities (32Q, 32V).

A gen-tie to a solar or BESS plant breaks the symmetry. The utility end is still strong. The collector end is an inverter-based resource. Its fault current is typically about 1.0–1.5 pu of rating, set by the OEM current limit, after a sub-cycle transient that can be higher (take the actual value from the OEM short-circuit model), and its phase angle comes from control firmware. In positive and negative sequence, the collector terminal looks like a programmable current source.

This module shows that the zero-sequence network is different. The inverters sit behind the MPT's delta LV winding, so they are invisible in HV zero sequence. The collector-end zero-sequence source is just the main power transformer's grounded-wye neutral, which is passive, linear and predictable. Good IBR tie-line ground protection is built on that one fact.

Assumed configuration: a 230 kV gen-tie to one YNd MPT (grounded-wye HV, delta 34.5 kV LV). The pad-mount arrangement on the collector (see the configurations table in Module 1.2) does not change the HV zero-sequence picture, because the MPT delta blocks it. A YNyn MPT, an autotransformer with a tertiary, or extra grounded-wye transformers on the HV bus do change it; the lab's "second grounded source" option shows one such case.

Failure modes

Three ways conventional elements fail near IBRs

1. Line current differential (87L): non-homogeneous angles

87L compares the current entering each end. For an internal fault both currents point into the line, so the ratio k=Iremote/Ilocalk = I_{remote}/I_{local} sits near the positive real axis. (The lab below takes the strong terminal U as local, so k=IC/IUk = I_C/I_U.) With an IBR at one end, the angle of its current, especially its negative-sequence current, is whatever the controller chooses. If that angle swings far enough, k lands in the alpha-plane blocking region and the element restrains on an internal fault. A weak infeed with a small |k| is not the problem, because the blocking region excludes |k| < 1/R. A rotated infeed is.

Interactive lab
87L alpha plane: a controlled source moves the internal-fault point
For an internal fault, the ratio k = I_remote / I_local should sit near the positive real axis. With an IBR at one end, the angle of k is set by the converter's controls, not by system impedance angles.
Element
95°
50%
195°
-6-4-20246-6-4-20246Re(k)Im(k)ideal internalthrough-fault
|k|
0.25
∠k
-0°
Operates: k is outside the blocking region
blocking (restraint) regionmeasured ratio k

A weak terminal by itself is harmless: a small |k| falls inside the inner radius 1/R and the element operates. The danger is a converter whose negative-sequence current is rotated far from the grid's. Select 87LQ and move the I₂ lead angle from the compliant +95° towards −85° (I₂ lagging V₂). k swings into the blocking region, and 32Q at the collector flips to reverse at the same time.

2. Ground distance (21G) and current-based phase selection (CFIDS)

Ground distance elements must know which loop (AG, BG, CG) to trust. Many relays select it by comparing the angle of I₂ to I₀ (CFIDS), supervised by a negative-sequence overcurrent threshold. At the IBR terminal I₀ is passive but I₂ is synthetic. It may be too small to pass the 50Q supervision, or rotated so the sector logic points at the wrong phase. Even when the loop is correct, fault resistance is magnified by the infeed ratio and tilted by the remote current's angle, so the mho circle under-reaches. For ground loops the magnification is modest (about 1–4× in the lab's model) because the MPT makes C strong in zero sequence; it is the phase loops, fed only by current-limited I₁ and I₂, that see the large weak-infeed ratios.

3. Negative-sequence directional (32Q) and the 50QF trap

Normally 50QF/50QR supervision is set just above the standing negative-sequence current from load unbalance and untransposed lines, typically a small fraction of load current. One documented IBR application ended up with a much higher 50QF ≈ 1,228 A. The course could not confirm that application's rationale. A plausible one is security of the weak-end 32Q against the plant's own I₂ injection during external faults, which an IEEE 2800 plant produces at up to its current limit. Treat the number as a "what goes wrong if" example, not a recommendation: with the plant's I₂ capped by its current limit and its control law, the collector terminal cannot be relied on to produce that much 3I₂. When it doesn't, 32Q, 67Q and CFIDS all go quiet together.

The fix

Exploit the passive zero-sequence network

Looking from the collector terminal into its own substation, the zero-sequence circuit is only the MPT's leakage impedance to ground. For any fault out on the line, the relay therefore measures

V0=−Z0,MPT I0⇒z0=Re⁡ ⁣[V0 (I0 1∠θL0)∗]∣I0∣2≈−∣Z0,MPT∣cos⁡(∠Z0,MPT−θL0)V_0 = -Z_{0,MPT}\, I_0 \quad\Rightarrow\quad z_0 = \frac{\operatorname{Re}\!\left[V_0\,(I_0\,1\angle\theta_{L0})^*\right]}{|I_0|^2} \approx -|Z_{0,MPT}|\cos(\angle Z_{0,MPT}-\theta_{L0})

The measured z₀ does not depend on the fault location, the fault resistance or the inverter firmware. A voltage-polarised zero-sequence directional element (32V) therefore has a fixed, predictable operating point. Because 3I₀ is not limited by the inverter's MVA rating, its supervision (50GF) can be set far below 50QF. The example methodology uses 600 A.

  • VFIDS: select the faulted loop from phase-voltage depression rather than the I₂/I₀ angle, so firmware cannot mislead it.
  • 67G: operate when 50GF picks up and either 32V or 32Q declares forward. 32Q still helps when the plant does produce a good I₂.
  • Z0F threshold: it must sit above every forward value z₀ can take and below every reverse value, with margin. Two approaches are in use. Some relays' automatic setting rules put Z0F at a positive value, roughly half the line's |Z0L| (about +36 Ω here), relying on reverse faults measuring a large positive z₀ (about +87.5 Ω for a bus fault behind C). This course's earlier, more conservative choice was half of −|Z0,MPT| (−8.8 Ω), close to the forward operating point. Check your relay's instruction manual for its actual rule. A positive Z0F relies on the remote terminal supplying the reverse-fault I₀, so it is secure only while U is in service; the lab's reverse check assumes it is.

What eats the margin is anything that moves the forward z₀ towards zero or the reverse z₀ down: other zero-sequence sources behind C (a second MPT or a grounded tertiary; grounded-wye station-service transformers too, though a small one has hundreds of ohms of Z0 and moves z₀ only slightly), CT and VT angle error, and mutual coupling. A second MPT (or a similarly stiff source) in parallel halves the impedance behind C, so line faults measure about −8.8 Ω. The forward margin of a −8.8 Ω Z0F then falls from about 2:1 to about 1:1, which is no margin at all: in the lab it fails by a few hundredths of an ohm, and any real angle error would make it fail outright. Try it in the lab.

Interactive lab
Tie-line SLG fault: what does the collector-end relay actually see?
Drag the AG fault along the 230 kV gen-tie and add fault resistance. The IBR plant behind the collector terminal is solved as a current-limited, dual-sequence current source; the MPT gives a purely passive zero-sequence path. Every ground element at relay C re-evaluates live, and the coverage maps sweep all locations × Rf for the current settings.
50%
0 Ω
IBR negative-sequence control
95°
IEEE 2800-2022 window for full-converter IBRs (Cl. 7.2.2.3.4; verify against the standard): I₂ leads V₂ by 90°–100°. Simulate a bad firmware change at −85° (I₂ lagging). At 20° or 170° this network absorbs part of the rotation and CFIDS still selects A.
300 MVA
Rated current 753 A at 230 kV; I_max 1.1 pu
1228 A
600 A
Zero-sequence sources behind C
-8.8 Ω
Forward if z₀ < Z0F, reverse if z₀ > Z0F + 1 Ω. Line faults measure z₀ ≈ −17.6 Ω (MPT only) or −8.8 Ω (second grounded source in parallel); a bus fault behind C measures ≈ +87.5 Ω.
120 %
UTILITY (U)strong source230 kV gen-tie · Z1L = 24.1 Ω · Z0L = 72.4 Ωrelay CMPT YNdZ0T pathIBR plantI₁, I₂ controlledAG · Rf 0 Ω50 % from U→ 3I₀ 3,149 A from U← 3I₀ 3,004 A← 3I₂ 1,243 A
Legacy (CFIDS + 32Q, 50QF-supervised): detects forward ground fault
IBR-aware (VFIDS + 32V/67G, 50GF-supervised): detects forward ground fault
3I₀ at C
3,004A
3I₂ at C
1,243A
|V₂| / |V₀| at C
34.5 / 17.6kV
32V reverse check
REV ✓
HV bus fault behind C: z₀ ≈ +87.5 Ω
IBR Iq₁ · I₂ · Ip
0.55 · 0.55 · 0.00pu
V₁ 0.74 pu, V₂ 26 %
ElementMeasured at CLegacy: CFIDS · 32QIBR-aware: VFIDS · 32V
50QF
3I₂ forward supervision
1,243 A vs 1,228PICKUPnot req'd
50GF
3I₀ forward supervision
3,004 A vs 600—PICKUP
CFIDS
∠(I₂/I₀) sector
1°AGbackup
VFIDS
lowest phase voltage
Va 46.2 kV—AG
32Q
z₂ vs Z2F
z₂ -83.2 ΩFWDFWD
32V
z₀ vs Z0F
z₀ -17.5 Ω—FWD
21G Z2
mho 120% of Z1L
12.1∠84° ΩOPERATEOPERATE
67G / 67Q
directional ground O/C
FWD TRIPFWD TRIP
21G AG loop at C (R–X, primary Ω)
-200204060-10010203040R (Ω)X (Ω)Z1LZ_AG

Rf is magnified by the ratio of total fault current to the IBR-end current, pushing Z_AG far to the right of a mho circle. This is why the weak end relies on directional overcurrent (67G) and pilot schemes, not distance, for resistive faults.

Currents at C (phase-A reference)
0°90°180°-90°I₁I₂I₀V₂V₀
positive seqnegative seqzero seqvoltages (scaled)
Coverage · legacy CFIDS + 32Q66% full · 66% forward
UCfault location →40Ω0Ω
Coverage · VFIDS + 32V/67G93% full · 99% forward
UCfault location →40Ω0Ω
forward + correct phase selectedforward, phase selection failsno forward declaration
Security

Zero-sequence mutual coupling

Transmission corridors are crowded. If the tie-line shares towers or a right-of-way with another circuit, a ground fault on that circuit induces a zero-sequence EMF along the tie-line. The induced EMF is inside the line, so both terminals see zero-sequence current flowing in from their own source. Both z₀ values go negative and both 32V elements declare forward. To a POTT scheme built only on 32V, that looks exactly like an internal fault. (The lab models only this induced component; in a connected grid a conductive component also flows, so the real magnitude needs a coupled-network study.)

Interactive lab
Zero-sequence mutual coupling: an induced current that looks internal
An SLG fault on a parallel utility line induces a zero-sequence EMF along the healthy tie-line. The resulting loop current flows through the utility source at U and the MPT neutral at C, and both ends' zero-sequence directional elements see it as forward.
95%
0.60
Representative double-circuit values are roughly 0.4–0.7; the real figure depends strongly on tower geometry and earth resistivity.
600 A
shared right-of-way · zero-sequence mutual Z0MUC (IBR)tie-line U–C (healthy)keys PTkeys PTinduced circulating 3I₀ = 628 APRparallel utility line P–R (different substations)external SLG
Parallel-line fault 3I₀
7,422A
Induced 3I₀ in tie-line
628A
z₀ at U
-15.1Ω
= −|Z0S| ⇒ forward
z₀ at C
-17.5Ω
= −|Z0,MPT| = −17.6
FALSE TRIP: both terminals declare forward and exceed 50GF, so the POTT scheme trips the healthy tie-line.
Induced 3I₀ vs. fault position on the parallel line
02040608010002505007501k1.25k1.5kfault position on parallel line (%)3I₀ (A)50GF 600 A
induced 3I₀50GF pickup

With identical sources at P and R, the induced EMF from the two halves of the parallel line cancels for a mid-line fault. The worst case is a fault at either end of the parallel line, where nearly all of its 3I₀ flows along the coupled length in one direction. Always check the end-of-line faults on every coupled circuit.

Model limitation: the parallel line is treated as galvanically separate from the tie-line, so only the induced loop current is shown. In a real grid P, R and U are usually connected, and the external fault also drives conductive I₀ out of the MPT neutral, through the tie-line towards the fault: it reads reverse at U and forward at C. At C it adds to the induced component; at U it competes with it, so security rests on U's directional decision, and this lab may overstate or understate the false-trip risk. The 600 A example 50GF fails in this illustrative corridor; whether it fails in yours takes a coupled-network short-circuit study.

MitigationHow it helpsCost
50GF above max induced 3I₀Induced current never reaches pickupReduces Rf coverage for real faults. In this example it can't be combined with 40 Ω coverage (see below)
32Q supervision at the strong endNegative-sequence mutual coupling is small, and the induced loop current carries no I₂; any conductive I₂ from the external fault most likely reads reverse at UStrong end must have adequate I₂; it usually does
Mutual-coupling-aware 32V thresholdsSome methodologies bias forward/reverse thresholds for the voltage-inversion cases of particular topologiesRequires a full coupled-network study; follow manufacturer guidance
87L with zero-sequence-free characteristicDifferential is inherently immune to induced external current through the zoneNeeds a reliable channel and IBR-aware alpha-plane settings

The first two rows pull against each other in this example. Covering every fault up to 40 Ω (challenge task 3) needs 50GF at or below about 509 A, the smallest 3I₀ at C (a 40 Ω fault next to U). The worst-case induced 3I₀ at Z0M/Z0L = 0.6 is about 712 A, so no single 50GF pickup is both dependable and secure. Here 32Q supervision at U is mandatory, not optional.

Other terminal

At the utility end

The strong terminal has its own problems, and they come from the same MPT.

  • Zone 2 reaches into the plant. On a short gen-tie, a 120 % Zone 2 at U reaches through the line and into the MPT (with this module's impedances, about a quarter of the way through it) and, on very short lines or with minimum-reach rules, possibly the 34.5 kV collector. The plant's small infeed hardly reduces that reach. Coordinate it with the MPT 87T and backup protection and with the collector bus and feeder protection, or time-delay it accordingly.
  • The MPT is a ground source on the utility system. For line ground faults the MPT neutral supplies part of 3I₀, so U sees less than the total. For faults elsewhere on the utility system, the YNd MPT feeds I₀ back through the line. The utility's ground-relay coordination must include the MPT as a zero-sequence source, and must be checked with the MPT in and out of service.
  • Transformer-terminated lines. For very short gen-ties, some designs use one differential zone covering the line and the MPT (for example 87L with the transformer inside the zone), which can remove the MPT HV breaker. It is a design choice to agree with the transmission owner.

IEEE C37.246 (guide for protection of transmission-to-generation interconnections) covers these interconnection questions, and the IEEE PES technical report on IBR impacts on transmission protection (cited by this course as PES-TR81; verify the report number and edition) covers the IBR-specific behaviour.

Reclosing

Reclosing and synchronism with an IBR plant

With POTT both ends normally trip for a gen-tie fault. If the C breaker fails to open or is slow, the plant is left islanded on the line when U opens, and U must not reclose onto a line the plant may still be energizing. The usual safeguards are dead-line supervision (27 on a line-side VT) or synchronism check (25) at U, a direct transfer trip from U to the plant, and a reclose dead time longer than the plant's worst-case trip or cessation time. These must be coordinated with the plant's anti-islanding and ride-through settings (IEEE 2800 and PRC-029-1 keep it online for faults elsewhere). A failed reclose is also a second voltage dip for other IBR plants nearby (this plant is already disconnected), and it counts toward their consecutive-deviation rules in Module 3.2. Single-pole tripping and reclosing with IBR plants is an active area: how a converter behaves during the open-pole interval is OEM-specific, so check with the OEM before applying it.

Synthesis

Recommended settings philosophy (example)

FunctionLegacy practiceIBR-aware practice at collector terminal
Faulted-phase selectionCFIDS (∠I₂/I₀ + 50Q)VFIDS (voltage depression + 50G)
Ground directional32Q only32V (zero-seq impedance) OR 32Q
Ground O/C supervision50QF ≈ 1,228 A (example)50GF ≈ 600 A (example), set above induced 3I₀
Distance21G zone 1/2 for all faults21G for low-Rf faults only; 67G + pilot for resistive faults
Pilot schemeDCB or POTTPOTT + weak-infeed echo & trip (Module 4.2)
DifferentialDefault alpha-planeValidate 87LA/87LQ against OEM I₂ behaviour; review with the OEM and relay vendor whether 87LQ should stay enabled if I₂ is not regulated
Example values are representative of one published application; your settings must come from a system-specific study.
Key takeaways
  • Positive- and negative-sequence quantities at an IBR terminal are set by firmware, and are small and possibly rotated.
  • Zero sequence at the collector terminal is passive: V₀ = −Z0,MPT·I₀, so z₀ ≈ −|Z0,MPT| for every line fault (more precisely, −|Z0 of everything grounded behind C|).
  • Moving to 50GF, 32V, 67G and VFIDS restores resistive ground-fault coverage that 50QF/32Q/CFIDS lose.
  • Mutual coupling can make both ends' 32V declare forward for an external fault. Use pickup margin and negative-sequence supervision at the strong end.
  • Check coverage across location × Rf × IBR control mode, and treat inverter firmware changes as protection changes.
  • At the utility end, coordinate Zone 2 with the plant's MPT protection, treat the MPT as a ground source, and supervise reclosing with dead-line or sync-check.
Assessment

Knowledge check

0/7 answered
  1. Q1
    Why is the zero-sequence network behind the collector-end relay considered 'passive and linear'?
  2. Q2
    At the collector terminal, what value does the impedance-based zero-sequence directional quantity z₀ measure for any fault out on the line?
  3. Q3
    A 300 MVA IBR plant (I_max = 1.1 pu) hits its current limit during a bolted fault and shares the budget equally (ΔIq₁ ≥ ΔIq₂). Roughly what 3I₂ does it deliver at 230 kV?
  4. Q4
    Why does a conventional 21G mho element at the IBR terminal under-reach badly for resistive faults?
  5. Q5
    CFIDS selects the faulted phase from the angle between I₂ and I₀. What makes it unreliable at an IBR terminal?
  6. Q6
    On a tie-line sharing a corridor with another utility line, what is the main security risk to a 32V/67G POTT scheme?
  7. Q7
    Why is POTT with weak-infeed logic preferred over a pure distance scheme on an IBR tie-line?
Mastery challenge

Restore 40 Ω coverage without sacrificing security

You are reviewing the collector-end relay of a 230 kV gen-tie to a 300 MVA BESS. The previous engineer used CFIDS, 32Q and a 1,228 A 50QF. Use the two labs to produce a defensible setting set.

Finished this module?
Your progress is saved in this browser only.