TAP scaling, dual-slope restraint, and harmonic security.

You will be able to
  • ▸Calculate TAP factors on a chosen MVA base
  • ▸Set O87P, SLP1, SLP2 and 87U from OLTC range, CT error and saturation
  • ▸Use 2nd-harmonic restraint for inrush and 5th-harmonic for overexcitation
  • ▸Explain why REF out-performs 87T for faults near the neutral
Standards
IEEE C37.91-2021IEEE C37.110IEEE C57.109
Start here

What goes in must come out, after you account for the transformer

A differential relay applies Kirchhoff's current law to a protected zone. Measure every current entering and leaving the zone; if they don't sum to zero, current is going somewhere it shouldn't, and that is a fault inside the zone. For a bus or a line, that is nearly the whole story.

A transformer is harder because, even with nothing wrong, the currents on its two sides do not simply cancel:

  • Different magnitudes. The 34.5 kV side carries several times the current of the HV side, measured through CTs of different ratios.
  • Phase shift. A YNd1 MPT shifts the LV currents by 30°.
  • Zero sequence. A grounded-wye winding can carry I₀ that the delta side never sees.
  • Magnetising current flows only on the energised side: small in steady state, enormous during inrush or overexcitation.
  • On-load tap changers change the ratio in service, so the "balance" you set on day one does not hold at every tap.
  • CT errors, small in steady state and large if a CT saturates (Module 2.3).

Every 87T setting exists to manage one of those effects. This module walks through them in order, with the operate–restraint plane as the central picture.

Step 1

TAP scaling: putting both windings on one per-unit base

A numerical relay first scales each winding's secondary current by a TAP so that rated power on a chosen MVA base reads 1.0 pu on every winding:

TAPn=MVAbase×10003 Vn (kV)×CTRn\mathrm{TAP}_n = \frac{\mathrm{MVA}_{base}\times 1000}{\sqrt3\, V_{n}\,(\text{kV}) \times \mathrm{CTR}_n}

It also applies internal phase-angle compensation for the vector group and removes zero-sequence current from any grounded-wye winding, so an external ground fault on the HV system does not look like differential current. That is why modern practice connects every CT in wye and lets the relay compensate, rather than delta-connecting CTs as electromechanical schemes did.

Worked example

A representative collector MPT is rated 100/133/167 MVA (ONAN/ONAF/ONAF), 230/34.5 kV YNd1. It has 1200:5 multi-ratio HV bushing CTs used at full ratio and 3000:5 LV CTs. Compute the TAPs on a 100 MVA base and a 167 MVA base. What does O87P = 0.30 pu mean in primary MVA on each?

Interactive lab
TAP Calculator & MVA-Base Consistency
The relay scales each winding's secondary current by its TAP so that rated power on the chosen MVA base reads 1.0 pu on every winding. Every differential setting is then entered in multiples of TAP.
100 MVA
167 MVA
HV winding kV
1200:5
LV winding kV
3000:5
CT secondary
0.30 pu
TAP 1 (HV)
1.05A
TAP 2 (LV)
2.79A
TAP max/min
2.67
relay-specific; ≤ 7.5 is common
Top rating
1.67pu
167 MVA on 100 MVA base
O87P HV side
0.31A sec
O87P LV side
0.84A sec
O87P in MVA
30.0MVA
primary-equivalent
O87P at top rating
0.18pu
of top-rating current
BaseTAP 1TAP 2O87P 0.30 pu = …
100 MVA (chosen base)1.05 A2.79 A30.0 MVA primary
167 MVA (top rating)1.75 A4.66 A50.1 MVA primary
Same transformer, same CTs, two MVA bases. The TAPs scale linearly with the base, so an O87P of 0.30 pu is a primary pickup 67% higher on the top-rating base than on the 100 MVA base.
TAPs are within a typical relay range and spread. Choose the base once, then enter every setting on it consistently.
Step 2

The dual-slope characteristic

The relay computes an operate quantity and a restraint quantity for each phase. This lab uses the average-magnitude definition (others use maximum or sum; check your relay):

IOP=∣I⃗W1+I⃗W2∣IRT=12(∣I⃗W1∣+∣I⃗W2∣)I_{OP} = \left|\vec I_{W1} + \vec I_{W2}\right| \qquad I_{RT} = \tfrac12\left(|\vec I_{W1}| + |\vec I_{W2}|\right)

Here I⃗W1\vec I_{W1} and I⃗W2\vec I_{W2} are the TAP-scaled, compensated winding currents, not the positive- and negative-sequence currents I1,I2I_1, I_2 used elsewhere in the course.

A through-current with perfect CTs gives IOP=0I_{OP}=0. An internal fault fed from one side gives IOP=2IRTI_{OP} = 2I_{RT}. The characteristic sits between the two:

SettingTypical rangeRepresentativeWhat it guards against
O87P minimum pickup0.15–0.40 pu0.20–0.30 puSteady-state excitation current and small errors at light load
SLP115–40%25–35%Proportional errors: OLTC range plus CT ratio error
IRS1 breakpoint2–4 pu3 puWhere CT saturation becomes credible
SLP250–100%60–85%Asymmetric CT saturation on heavy through-faults
87U unrestrained8–12 pu10 puSevere internal faults, cleared without harmonic delay
2nd-harmonic block10–25%15%Energisation and sympathetic inrush
5th-harmonic block25–45%35%Overexcitation (with 24 as the primary protection)
Representative values from IEEE C37.91-2021 practice and manufacturer guides. Always use your relay's definitions.

Sizing SLP1 from the tap changer

Suppose the same 230 kV MPT has an HV on-load tap changer spanning 195.5–253 kV (a representative range; many MPTs have a de-energised tap changer instead, with a much smaller in-service error). Relative to the nominal ratio used for TAP:

253−230230=+10%,195.5−230230=−15%\frac{253-230}{230} = +10\%,\qquad \frac{195.5-230}{230} = -15\%
Interactive lab
87T Operate–Restraint Plane & Harmonic Lab
External fault with CT saturation. Same through-fault, but the low-side CT saturates after about 1.5 cycles because of DC offset (Module 2.3). The false operating current grows over several cycles, then recovers as the offset decays. Watch the trajectory climb the restraint plane.
Scenario injector
Correct outcomes: 7/9
10.00 pu
87T settings (pu of TAP)
0.30
30%
3 pu
60%
10 pu
Harmonic security
15%
35%
Relay decision
TRIP
TRIP: restrained 87T
Expected
NO TRIP
out-of-zone / non-fault
Peak IOP
4.50pu
Peak IOP / IRT
58%
apparent slope
Operate vs restraint (worst phase)
characteristictrajectory (cycles)
0246810120123456IRT restraint (pu TAP)IOP operate (pu TAP)OPERATERESTRAIN87U 10 pu ↑ (off scale)c1c5c10
Harmonic content (% of fundamental)
01020304050%9632nd3214th4325th
ABCblock threshold
TRIP: restrained 87T (cycle 5). Misoperation on an event the transformer should ride through: security failure.
Step 3

Harmonics: telling inrush and overexcitation from faults

Inrush. Energising a transformer at an unfavourable point on the voltage wave, especially with remanent core flux, drives the core into saturation for part of each cycle. IEEE C37.91 and manufacturer literature put the instantaneous peak at roughly 8–30× rated current depending on size and design (12–15× is commonly cited for large units; treat these as representative), decaying over hundreds of milliseconds to seconds. It flows on one side only, so it is all differential current. The waveform is asymmetric and rich in 2nd harmonic, which is the basis for 2nd-harmonic blocking or restraint.

Overexcitation. High voltage or low frequency (V/Hz above about 1.05–1.10 pu) saturates the core symmetrically. The exciting current carries odd harmonics; the 3rd is trapped in delta windings and removed by zero-sequence filtering, so the 5th harmonic is the usable signature.

Step 4

Restricted earth fault (87N): the faults 87T cannot see

For a ground fault at a fraction xx of the way from the neutral of a grounded-wye winding, the driving voltage is only xx of phase voltage, and only xx of the turns couple the fault current to the line side. The phase current change scales roughly as x2x^2, and 87T's zero-sequence removal subtracts a further third. Faults in the bottom 20–30% of the winding can be invisible to 87T.

REF compares the neutral CT current with the residual sum of the phase CTs (3I03I_0) for that winding only. It is supervised directionally and checked for CT saturation, and it sees a current proportional to xx. REF matters most on impedance-grounded windings where fault current is limited.

Interactive lab
REF (87N) vs 87T Sensitivity Along the Winding
Model of a grounded-wye winding with a ground fault x% of the way from neutral to terminal. Fault current in the shorted turns grows roughly ∝ x (driving voltage ∝ x), and the current reflected into the phase CTs is ∝ x² and reduced by zero-sequence removal. The neutral CT used by REF sees the fault current directly.
15%
4 pu
Set by grounding impedance; low for resistance-grounded
0.30 pu
0.10 pu
87T operate
0.060pu
misses
REF operate
0.600pu
detects
87T winding coverage
66%
REF winding coverage
98%
87T operate ∝ x²REF operate ∝ xO87PREF pickup
02040608010001234Fault position from neutral (%)Operate (pu)87T blind zone

Simplified, resistance-grounded-style approximation for teaching. On a solidly grounded winding the fault current near the neutral stays higher because winding leakage reactance falls too, but the phase-side reflection still shrinks with x. Both curves are on a common per-unit base for comparison.

Step 5

Overexcitation (24) and the rest of the MPT suite

The 5th-harmonic block keeps 87T secure during overexcitation, but something still has to protect the core. That is the Volts-per-Hertz element (24), usually a definite-time alarm stage plus an inverse-time trip stage, coordinated below the manufacturer's overexcitation capability curve.

Interactive lab
Volts-per-Hertz (24) Coordination
Flux in the core is proportional to V/f. Above roughly 1.05 pu at full load (1.10 pu at no load, per IEEE C57.12.00) the core saturates, stray flux heats structural steel, and damage accumulates with time. Coordinate an inverse-time 24 element below the transformer's withstand curve but above its continuous capability.
1.06 pu
40
t = 0.003·TD / (M/PU − 1)²
Trip at 1.08 pu
337s
unloaded MPT, inside no-load capability
Trip at 1.10 pu
84.3s
withstand 1200 s
Trip at 1.20 pu
6.9s
withstand 30 s
Min margin
1.3×
withstand ÷ trip time
Pickup vs continuous
secure
≥ 1.05 pu (full-load limit)
transformer withstand (representative, loaded)24 inverse-time trip
11.051.11.151.21.251.31.351.41.450.11101001k1e4V/Hz (pu)Time (s)continuous
Coordinated: the 24 element clears every overexcitation level before the withstand limit is reached.

Open question: loaded vs unloaded. The pickup check above uses the 1.05 pu full-load limit. At a collector the MPT often sits energised overnight with no load, while cable charging lifts the 34.5 kV voltage, and C57.12.00 allows up to 1.10 pu continuously at no load. A pickup below 1.10 pu (the lab default is 1.06 pu) can therefore time out on a healthy, unloaded MPT: watch the 1.08 pu readout. Practices differ: some set the inverse-time pickup against the no-load limit, others keep it lower and rely on a definite-time alarm stage (not modelled here) plus operating procedures. Agree the basis with the transformer manufacturer and your utility.

Withstand curve is illustrative only. Always coordinate against the manufacturer's overexcitation capability curve, and against the generator's where the MPT is a GSU.

The complete MPT package in a collector substation typically includes: dual-slope 87T with 87U, REF on grounded-wye windings, 24, sudden pressure (63) and other mechanical devices (gas accumulation, oil and winding temperature), backup phase and ground overcurrent (50/51, 51G on the neutral), and HV breaker-failure logic that keys direct transfer trip to the remote utility terminal.

Key takeaways
  • TAP = MVA·1000/(√3·kV·CTR). Choose one MVA base and keep every per-unit setting on it.
  • SLP1 covers proportional errors: tap range plus CT ratio error. Size it on the actual restraint definition, not just the sum of percentages.
  • SLP2 (or an external-fault detector) provides security against CT saturation on heavy through-faults.
  • 2nd harmonic indicates inrush; 5th indicates overexcitation. Cross-blocking protects against low-H2 phases.
  • 87U sits above the inrush fundamental and saturated through-fault error, around 8–10 pu of TAP.
  • REF covers near-neutral winding faults where 87T sensitivity collapses as x².
  • A grounding bank inside the 87T zone makes the LV side a zero-sequence source: remove I₀ on that winding too, and use the bank neutral CT for LV REF.
Assessment

Knowledge check

0/7 answered
  1. Q1
    A 230/34.5 kV MPT uses 1200:5 HV CTs and 3000:5 LV CTs. What is TAP1 on a 100 MVA base?
  2. Q2
    An OLTC regulates +10% / −15% around nominal, and the CTs may contribute up to 10% ratio error. What is a defensible SLP1?
  3. Q3
    Why does SLP2 need to be much steeper than SLP1?
  4. Q4
    During energisation, phase B shows only 11% 2nd harmonic while A and C show 24% and 17%. PCT2 is 15%. What prevents a trip?
  5. Q5
    What signature distinguishes overexcitation from inrush?
  6. Q6
    Where should the unrestrained 87U element be set?
  7. Q7
    Why does REF (87N) out-perform 87T for a ground fault 10% from the neutral of a grounded-wye winding?
Mastery challenge

Commission a secure, dependable 87T

Using the labs, produce a complete 87T / 87N / 24 setting set for the 230/34.5 kV, 100/133/167 MVA collector MPT from Step 1, with a +10% / −15% OLTC. Your target in the operate–restraint lab is 8 of 9 scenarios correct. The ninth, the near-neutral fault, is impossible for 87T by design and must be covered by REF.